Switch Mode Power Supplies
Switch Mode Power Supplies. This modular, high-frequent 19″ Switch-mode power supplies can deliver power ratings up to 25 kW and 500VDC output including a standardized analogue interface. EMC-compliant and rounded-up with a high-tech finish. Therefore, these Modules and Plug-in Units are intended for the installation in an industrial control cabinet.
This modular, high-frequent 19" Switch-mode power supplies can deliver power ratings up to 15 kW and 500VDC output voltage including a standardized analogue interface. EMC-compliant and rounded-up with a high-tech finish. Therefore the AC315DC Modules and Plug-in Units are intended for the installation in an industrial control cabinet. One of the outstanding features of this compact power supply is the constant low ripple. It provides excellent DC quality.
The devices are short-circuit proof and resistant against over temperatures. This is beyond:
- galvanically isolated setpoint;
- actual values (0-10 VDC);
- optional 0-20 mA;
- 4-20 mA;
- Profibus DP.
EDI:
The DeionX Switch Mode Power Supplies are specifically selected to be used for Electro Deionisation (EDI). During the last 20 years DeionX engineers reviewed and tested many power supplies and selected these power supplies as a reliable and simple solution for large scale EDI applications. Over the years, the combination of the DeionX Switch Mode Power Supplies with E-Cell or Ionpure EDI proved to be efficient and cost effective on many ultrapure water systems.
The DeionX Switch Mode Power Supplies sets a new standard for flexible, reliable, AC/DC power systems in OEM, Industrial applications.
Especially adapted for Multiple Output Rectifier Cabinets the DeionX Modules and Plug-in Units offer a high packaging density. Furthermore they features a central feed-in as well as a central interface for communication and cooling.
Due to the customer-specific design the Multiple Output Rectifier Cabinets are particularly efficient.
Five functions:
The switch-mode rectifier features the following five functions:
- Firstly, high-frequent disturbances reduces in the mains filter. On the other hand, it uses the mains filter to dampen the interference voltages.
- Secondly, the mains rectifier converts the AC voltage into DC voltage.
- Thirdly, the power electronics then convert the DC voltage pulse width modulated into a staircase-shaped alternating voltage.
- Next, the internal transformer stands for a galvanic potential separation and voltage adjustment on the secondary side.
- Lastly, fast power diodes, what generates a constantly smoothed and fully controllable DC voltage, achieves side rectification on the output side.
Interfaces:
The standard interfaces for setpoints and actual values reading are 0-10 V. Optional we can supply these interfaces as 0-20 mA or 4-20 mA signals.
Panel Description
Terminal Strip X01
Terminal X01 | Description | Voltage |
1 | Phase 1 | EU 3 x 400 VAC ± 10%, 47-63 Hz
USA 3 x 460 VAC ± 10%, 47-63 Hz |
2 | Phase 2 | |
3 | Phase 3 | |
4 | GND |
Terminal Strip X02
Terminal X02 | Description | Standard | Optional |
1 | Reference Voltage | 10 V DC | N/A |
2 | Reference Voltage | 10 V DC | N/A |
3 | Set Voltage Value | 0 …10 V DC | 0(4) … 20 mA DC |
4 | Set Current Value | 0 …10 V DC | 0(4) … 20 mA DC |
5 | GND | GND | GND |
6 | GND | GND | GND |
7 | not used | ||
8 | not used | ||
9 | Actual Voltage | 0 … Nominal Voltage | only with U<100V |
10 | direct | ||
11 | Actual Current
standardized |
0 …10 V DC
GND |
0(4) … 20 mA DC
GND |
12 | |||
13 | Pulse Enable | 13-14 closed
= Output active |
|
14 | |||
15 | Actual Voltage
standardized |
0 …10 V DC
GND |
0(4) … 20 mA DC
GND |
16 |
* Depending on the rectifier different options for monitoring and setting the values are available.
Terminal Strip X03
Terminal X03 | Description | |
1 | Main contactor ON (L, + ) | *230 VAC or 24 VDC |
2 | Main contactor OFF (N, – ) | |
3 | Feedback | 3&4 closed => contactor ON |
4 | Main contactor | 3&4 open => contactor OFF |
14 | Fault Contact | NC 14&16 closed => failure |
15 | Fault Contact | NO 15&16 closed => no failure |
16 | Fault Contact | Common |
* Depending on customer preference the main contactor is controlled with 230 VAC or 24 VDC. This needs to be specified on order!
Applications
DeionX power supplies are designed for demanding applications.
Common controls are shared across all platforms.
The DeionX Switch Mode Power Supplies are specifically selected to be used for Electro Deionisation (EDI). During the last 20 years DeionX engineers reviewed and tested many power supplies and selected these power supplies as a reliable and simple solution for large scale EDI applications. Over the years, the combination of the DeionX Switch Mode Power Supplies with E-Cell or Ionpure EDI proves to be efficient and cost effective on many ultrapure water systems.
In addition to EDI systems, DeionX switch mode power supplies can be used for many other applications like:
- Electro Separation Technologies as:
- Electro Dialysis (ED)
- Electro Dialysis Reverse (EDR)
- Electro DeIonization (EDI)
- Modern electrochemical processes
- Any industrial application that requires stable DC power
Specifications
Electrical data | AC315DC | AC325DC | ||||||
Mains Voltage EU
US |
3 x 400 VAC ± 10%, 47-63 Hz | 3 x 400 VAC ± 10%, 47-63 Hz | ||||||
3 x 460 VAC ± 10%, 47-63 Hz | 3 x 460 VAC ± 10%, 47-63 Hz | |||||||
Mains Current | 26.7 A | 45 A | ||||||
Mains Power | 18.4 kVA | 31 kVA | ||||||
Nominal DC Voltage | 300 | 400 | 500 | VDC | 300 | 400 | 500 | VDC |
Nominal DC Current | 50 | 37,5 | 30 | ADC | 83,5 | 62,5 | 50 | ADC |
Control Voltage | 24 VDC or 230 VAC | 24 VDC or 230 VAC | ||||||
Efficiency | up to 90% | up to 90% | ||||||
Ripple | < 3% referred to nominal values | < 3% referred to nominal values | ||||||
Adjustment ranges | 0 to 100% of nominal output | 0 to 100% of nominal output | ||||||
Set Voltage Value | 0…10 VDC or 0/4…20 mA DC | 0…10 VDC or 0/4…20 mA DC | ||||||
Set Current Value | 0…10 VDC or 0/4…20 mA DC | 0…10 VDC or 0/4…20 mA DC | ||||||
Control Accuracy | ±1% referred to nominal values | ±1% referred to nominal values | ||||||
Cooling | Forced air-cooled | Forced air-cooled | ||||||
Ambient Temperature | 0 to 45 ⁰C | 0 to 45 ⁰C | ||||||
Dimensions W / D / H | 490 / 443 / 276 mm | 490 / 443 / 276 mm | ||||||
Weight | 42 kg | 42 kg | ||||||
Protection grade | IP20 | IP20 |